RH-CSK-JMP-06
UQD06 Bypass Jumper, 24 in
Racks land weeks before servers do, and the manifold still has to be flushed, filled, and pressure-tested. This jumper drops into a supply and return manifold socket pair in place of a server loop, closing the circuit so you can run the CDU. 316L barb fittings with crimped 304 collars on reinforced EPDM hose; every jumper is pressure-decay tested in our shop before it is bagged. Standard build is plug-to-plug at 24 inches; other end configurations and lengths are configured-to-order.
| End fittings | UQD06 plug x UQD06 plug (other configs to order) |
| Hose | 3/8 in ID reinforced EPDM, 24 in overall length |
| Fittings | 316L stainless barbs, crimped 304 SS collars |
| Working pressure | Designed for 125 psi (8.6 bar) at 104 F (40 C) |
| Test | 100% pressure-decay tested at 100 psi before bagging |
| Temperature range | 34 F to 140 F (1 C to 60 C) |
| Flush flow | Passes flush flows to 20 LPM with minimal restriction |
| Fluid compatibility | PG25, treated DI water |
| Country of origin | USA (Van Alstyne, TX) |
RELATED: RH-CSK-CAP-04 → RH-CSK-CAP-06 → RH-CSK-CAP-08 → · All commissioning & service kits →